| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| The debugging feature on the Siemens CP 1604 and CP 1616 interface cards with firmware before 2.5.2 allows remote attackers to execute arbitrary code via a crafted packet to UDP port 17185. |
| SQL injection vulnerability in the login screen in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, allows remote attackers to execute arbitrary SQL commands via unspecified vectors. |
| Heap-based buffer overflow in the Siemens WinCC Runtime Advanced Loader, as used in SIMATIC WinCC flexible Runtime and SIMATIC WinCC (TIA Portal) Runtime Advanced, allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted packet to TCP port 2308. |
| The TELNET daemon in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not perform authentication, which makes it easier for remote attackers to obtain access via a TCP session. |
| Directory traversal vulnerability in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to read arbitrary files via crafted packets to TCP port 4999. |
| miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not properly handle URIs beginning with a 0xfa character, which allows remote attackers to read data from arbitrary memory locations or cause a denial of service (application crash) via a crafted POST request. |
| Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 does not properly copy fields obtained from clients, which allows remote attackers to cause a denial of service (exception and daemon crash) via long fields, as demonstrated by fields to the (1) open_session->workstation->NAME or (2) grant->VERSION function. |
| The integrated web server in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to execute arbitrary code via crafted packets to TCP port 4999. |
| CRLF injection vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via unspecified vectors. |
| Siemens SIMATIC WinCC OA before 3.12 P002 January uses a weak hash algorithm for passwords, which makes it easier for remote attackers to obtain access via a brute-force attack. |
| Siemens WinCC (TIA Portal) 11 uses a reversible algorithm for storing HMI web-application passwords in world-readable and world-writable files, which allows local users to obtain sensitive information by leveraging (1) physical access or (2) Sm@rt Server access. |
| Cross-site scripting (XSS) vulnerability in core/handleTw.php on the Siemens Enterprise OpenScape Branch appliance and OpenScape Session Border Controller (SBC) before 2 R0.32.0, and 7 before 7 R1.7.0, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. |
| Multiple cross-site scripting (XSS) vulnerabilities in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allow remote attackers to inject arbitrary web script or HTML via a (1) GET parameter, (2) POST parameter, or (3) Referer HTTP header. |
| Cross-site request forgery (CSRF) vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to hijack the authentication of arbitrary users for requests that modify data or cause a denial of service. |
| Siemens COMOS before 9.1 Patch 413, 9.2 before Update 03 Patch 023, and 10.0 before Patch 005 allows remote authenticated users to obtain database administrative access via unspecified method calls. |
| The integrated web server on Siemens SCALANCE X-200 switches with firmware before 4.5.0 and X-200IRT switches with firmware before 5.1.0 does not properly enforce authentication requirements, which allows remote attackers to perform administrative actions via requests to the management interface. |
| Buffer overflow in CCEServer (aka the central communications component) in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to cause a denial of service via a crafted packet. |
| The SNMP implementation in Siemens RuggedCom ROS before 3.11, ROS 3.11 for RS950G, ROS 3.12 before 3.12.4, and ROS 4.0 for RSG2488 allows remote attackers to cause a denial of service (device outage) via crafted packets. |
| The web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to obtain sensitive information or cause a denial of service via a crafted project file. |
| Cross-site scripting (XSS) vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary web script or HTML via unspecified vectors, a different vulnerability than CVE-2011-4511. |