| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes. |
| An issue was discovered in Schneider Electric Conext ComBox, model 865-1058, all firmware versions prior to V3.03 BN 830. A series of rapid requests to the device may cause it to reboot. |
| An information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system response to error provides more information than should be available to an unauthenticated user. |
| A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections. |
| An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved. |
| A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover. |
| A Violation of Secure Design Principles issue was discovered in Schneider Electric Modicon Modbus Protocol. The Modicon Modbus protocol has a session-related weakness making it susceptible to brute-force attacks. |
| An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack. |
| An issue was discovered in Schneider Electric homeLYnk Controller, LSS100100, all versions prior to V1.5.0. The homeLYnk controller is susceptible to a cross-site scripting attack. User inputs can be manipulated to cause execution of JavaScript code. |
| A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system accepts reboot in session from unauthenticated users, supporting a denial of service condition. |
| A vulnerability exists in Schneider Electric's Pro-Face GP Pro EX version 4.07.000 that allows an attacker to execute arbitrary code. Malicious code installation requires an access to the computer. By placing a specific DLL/OCX file, an attacker is able to force the process to load arbitrary DLL and execute arbitrary code in the context of the process. |
| Schneider Electric StruxureWare Data Center Expert before 7.4.0 uses cleartext RAM storage for passwords, which might allow remote attackers to obtain sensitive information via unspecified vectors. |
| A SQL injection vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can use calls to various paths allowing performance of arbitrary SQL commands against the underlying database. |
| An Uncontrolled Resource Consumption issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The uncontrolled resource consumption vulnerability could allow an attacker to exhaust the memory resources of the machine, causing a denial of service. |
| A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised. |
| An issue was discovered in Schneider Electric Tableau Server/Desktop Versions 7.0 to 10.1.3 in Wonderware Intelligence Versions 2014R3 and prior. These versions contain a system account that is installed by default. The default system account is difficult to configure with non-default credentials after installation, and changing the default credentials in the embedded Tableau Server is not documented. If Tableau Server is used with Windows integrated security (Active Directory), the software is not vulnerable. However, when Tableau Server is used with local authentication mode, the software is vulnerable. The default system account could be used to gain unauthorized access. |
| A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges. |
| A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server. |
| ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files. |
| Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems. |