| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device. |
| Cross-site scripting (XSS) vulnerability in the login form in the integrated web server on Siemens OZW OZW672 devices before 6.00 and OZW772 devices before 6.00 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. |
| The SSL layer of the HTTPS service in Siemens RuggedCom ROS before 4.2.0 and ROX II does not properly implement CBC padding, which makes it easier for man-in-the-middle attackers to obtain cleartext data via a padding-oracle attack, a different vulnerability than CVE-2014-3566. |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted Profinet packets. |
| Siemens SIMATIC HMI Comfort Panels before WinCC (TIA Portal) 13 SP1 Upd2 and SIMATIC WinCC Runtime Advanced before WinCC (TIA Portal) 13 SP1 Upd2 allow man-in-the-middle attackers to cause a denial of service via crafted packets on TCP port 102. |
| Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted PROFINET packets, a different vulnerability than CVE-2014-2253. |
| A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC IT Production Suite (All versions < V7.0 SP1 HFX 2), SIMATIC NET PC-Software (All versions < V14), SIMATIC PCS 7 V7.1 (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 V5.X (All versions < V5.5 SP4 HF11), SIMATIC WinCC (TIA Portal) Basic, Comfort, Advanced (All versions < V14), SIMATIC WinCC (TIA Portal) Professional V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) Professional V14 (All versions < V14 SP1), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1), SIMATIC WinCC V7.0 SP2 and earlier versions (All versions < V7.0 SP2 Upd 12), SIMATIC WinCC V7.0 SP3 (All versions < V7.0 SP3 Upd 8), SIMATIC WinCC V7.2 (All versions < V7.2 Upd 14), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 11), SIMATIC WinCC V7.4 (All versions < V7.4 SP1), SIMIT V9.0 (All versions < V9.0 SP1), SINEMA Remote Connect Client (All versions < V1.0 SP3), SINEMA Server (All versions < V13 SP2), SOFTNET Security Client V5.0 (All versions), Security Configuration Tool (SCT) (All versions < V4.3 HF1), TeleControl Server Basic (All versions < V3.0 SP2), WinAC RTX 2010 SP2 (All versions), WinAC RTX F 2010 SP2 (All versions). Unquoted service paths could allow local Microsoft Windows operating system users to escalate their privileges if the affected products are not installed under their default path ("C:\Program Files\*" or the localized equivalent). |
| The integrated web server on Siemens SCALANCE M-800 and S615 modules with firmware before 4.02 does not set the secure flag for the session cookie in an https session, which makes it easier for remote attackers to capture this cookie by intercepting its transmission within an http session. |
| Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D (All firmware versions < V6.00.046) and Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 for Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U (All firmware versions < V6.00.046) use a pseudo random number generator with insufficient entropy to generate certificates for HTTPS, potentially allowing remote attackers to reconstruct the corresponding private key. |
| The remote-management module in the (1) Multi Panels, (2) Comfort Panels, and (3) RT Advanced functionality in Siemens SIMATIC WinCC (TIA Portal) before 13 SP1 and in the (4) panels and (5) runtime functionality in SIMATIC WinCC flexible before 2008 SP3 Up7 does not properly encrypt credentials in transit, which makes it easier for remote attackers to determine cleartext credentials by sniffing the network and conducting a decryption attack. |
| The Siemens SPCanywhere application for Android does not properly store application passwords, which allows physically proximate attackers to obtain sensitive information by examining the device filesystem. |
| Siemens SICAM MIC devices with firmware before 2404 allow remote attackers to bypass authentication and obtain administrative access via unspecified HTTP requests. |
| The Siemens SPCanywhere application for Android does not use encryption during the loading of code, which allows man-in-the-middle attackers to execute arbitrary code by modifying the client-server data stream. |
| The Siemens SPCanywhere application for Android and iOS does not properly verify X.509 certificates from SSL servers, which allows man-in-the-middle attackers to spoof servers and obtain sensitive information via a crafted certificate. |
| Siemens SIMATIC STEP 7 (TIA Portal) before 13 SP1 determines a user's privileges on the basis of project-file fields that lack integrity protection, which allows remote attackers to establish arbitrary authorization data via a modified file. |
| Buffer overflow in the integrated web server on Siemens Ruggedcom WIN51xx devices with firmware before SS4.4.4624.35, WIN52xx devices with firmware before SS4.4.4624.35, WIN70xx devices with firmware before BS4.4.4621.32, and WIN72xx devices with firmware before BS4.4.4621.32 allows remote attackers to execute arbitrary code via unspecified vectors. |
| Open redirect vulnerability in the integrated web server on Siemens SIMATIC S7-1200 CPU devices with firmware before 4.1 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors. |
| A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.83; SIPROTEC 7UT686 : All versions < V 4.01; SIPROTEC 7SD686 : All versions < V 4.03; SIPROTEC 7SJ66 : All versions < V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained. |
| Siemens RUGGEDCOM ROS 3.8.0 through 4.1.x permanently enables the IP forwarding feature, which allows remote attackers to bypass a VLAN isolation protection mechanism via IP traffic. |
| Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows local users to gain privileges by leveraging weak system-object access control. |