Filtered by vendor Siemens
Subscriptions
Total
2183 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2016-9155 | 1 Siemens | 30 Ccid1445-dn18, Ccid1445-dn18 Firmware, Ccid1445-dn28 and 27 more | 2025-04-12 | N/A |
| The following SIEMENS branded IP Camera Models CCMW3025, CVMW3025-IR, CFMW3025 prior to version 1.41_SP18_S1; CCPW3025, CCPW5025 prior to version 0.1.73_S1; CCMD3025-DN18 prior to version v1.394_S1; CCID1445-DN18, CCID1445-DN28, CCID1145-DN36, CFIS1425, CCIS1425, CFMS2025, CCMS2025, CVMS2025-IR, CFMW1025, CCMW1025 prior to version v2635_SP1 could allow an attacker with network access to the web server to obtain administrative credentials under certain circumstances. | ||||
| CVE-2016-8672 | 1 Siemens | 8 Simatic Cp 343-1, Simatic Cp 343-1 Firmware, Simatic Cp 443-1 and 5 more | 2025-04-12 | N/A |
| A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server delivers cookies without the "secure" flag. Modern browsers interpreting the flag would mitigate potential data leakage in case of clear text transmission. | ||||
| CVE-2016-8564 | 1 Siemens | 1 Automation License Manager | 2025-04-12 | N/A |
| SQL injection vulnerability in Siemens Automation License Manager (ALM) before 5.3 SP3 Update 1 allows remote attackers to execute arbitrary SQL commands via crafted traffic to TCP port 4410. | ||||
| CVE-2016-9157 | 1 Siemens | 1 Sicam Pas\/pqs | 2025-04-12 | 9.8 Critical |
| A vulnerability in Siemens SICAM PAS (all versions before V8.09) could allow a remote attacker to cause a Denial of Service condition and potentially lead to unauthenticated remote code execution by sending specially crafted packets to port 19234/TCP. | ||||
| CVE-2016-4954 | 5 Ntp, Opensuse, Oracle and 2 more | 15 Ntp, Leap, Opensuse and 12 more | 2025-04-12 | 7.5 High |
| The process_packet function in ntp_proto.c in ntpd in NTP 4.x before 4.2.8p8 allows remote attackers to cause a denial of service (peer-variable modification) by sending spoofed packets from many source IP addresses in a certain scenario, as demonstrated by triggering an incorrect leap indication. | ||||
| CVE-2014-2909 | 1 Siemens | 6 Simatic S7 Cpu-1211c, Simatic S7 Cpu 1200 Firmware, Simatic S7 Cpu 1212c and 3 more | 2025-04-12 | N/A |
| CRLF injection vulnerability in the integrated web server on Siemens SIMATIC S7-1200 CPU devices 2.x and 3.x allows remote attackers to inject arbitrary HTTP headers via unspecified vectors. | ||||
| CVE-2016-7959 | 1 Siemens | 1 Simatic Step 7 | 2025-04-12 | N/A |
| Siemens SIMATIC STEP 7 (TIA Portal) before 14 improperly stores pre-shared key data in TIA project files, which makes it easier for local users to obtain sensitive information by leveraging access to a file and conducting a brute-force attack. | ||||
| CVE-2015-1448 | 1 Siemens | 5 Ruggedcom Firmware, Ruggedcom Win5100, Ruggedcom Win5200 and 2 more | 2025-04-12 | N/A |
| The integrated management service on Siemens Ruggedcom WIN51xx devices with firmware before SS4.4.4624.35, WIN52xx devices with firmware before SS4.4.4624.35, WIN70xx devices with firmware before BS4.4.4621.32, and WIN72xx devices with firmware before BS4.4.4621.32 allows remote attackers to bypass authentication and perform administrative actions via unspecified vectors. | ||||
| CVE-2016-7960 | 1 Siemens | 1 Simatic Step 7 | 2025-04-12 | N/A |
| Siemens SIMATIC STEP 7 (TIA Portal) before 14 uses an improper format for managing TIA project files during version updates, which makes it easier for local users to obtain sensitive configuration information via unspecified vectors. | ||||
| CVE-2015-1357 | 1 Siemens | 5 Ruggedcom Firmware, Ruggedcom Win5100, Ruggedcom Win5200 and 2 more | 2025-04-12 | N/A |
| Siemens Ruggedcom WIN51xx devices with firmware before SS4.4.4624.35, WIN52xx devices with firmware before SS4.4.4624.35, WIN70xx devices with firmware before BS4.4.4621.32, and WIN72xx devices with firmware before BS4.4.4621.32 allow context-dependent attackers to discover password hashes by reading (1) files or (2) security logs. | ||||
| CVE-2016-8565 | 1 Siemens | 1 Automation License Manager | 2025-04-12 | N/A |
| Siemens Automation License Manager (ALM) before 5.3 SP3 allows remote attackers to write to files, rename files, create directories, or delete directories via crafted packets. | ||||
| CVE-2015-3610 | 1 Siemens | 1 Homecontrol For Room Automation | 2025-04-12 | N/A |
| The Siemens HomeControl for Room Automation application before 2.0.1 for Android does not verify X.509 certificates from SSL servers, which allows man-in-the-middle attackers to spoof servers and obtain sensitive information or modify data via a crafted certificate. | ||||
| CVE-2014-8479 | 1 Siemens | 9 Scalance X-300, Scalance X-300 Series Firmware, Scalance X-300eec and 6 more | 2025-04-12 | N/A |
| The FTP server on Siemens SCALANCE X-300 switches with firmware before 4.0 and SCALANCE X 408 switches with firmware before 4.0 allows remote authenticated users to cause a denial of service (reboot) via crafted FTP packets. | ||||
| CVE-2016-7113 | 1 Siemens | 2 En100 Ethernet Module, En100 Ethernet Module Firmware | 2025-04-12 | N/A |
| A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 80/tcp could cause the affected device to go into defect mode. | ||||
| CVE-2016-5848 | 1 Siemens | 1 Sicam Pas\/pqs | 2025-04-12 | 6.7 Medium |
| Siemens SICAM PAS before 8.07 does not properly restrict password data in the database, which makes it easier for local users to calculate passwords by leveraging unspecified database privileges. | ||||
| CVE-2015-1599 | 1 Siemens | 1 Spcanywhere | 2025-04-12 | N/A |
| The Siemens SPCanywhere application for iOS allows physically proximate attackers to bypass intended access restrictions by leveraging a filesystem architectural error. | ||||
| CVE-2015-1594 | 1 Siemens | 5 Simatic Cfc, Simatic Prosave, Simatic Step 7 and 2 more | 2025-04-12 | N/A |
| Untrusted search path vulnerability in Siemens SIMATIC ProSave before 13 SP1; SIMATIC CFC before 8.0 SP4 Upd9 and 8.1 before Upd1; SIMATIC STEP 7 before 5.5 SP1 HF2, 5.5 SP2 before HF7, 5.5 SP3, and 5.5 SP4 before HF4; SIMOTION Scout before 4.4; and STARTER before 4.4 HF3 allows local users to gain privileges via a Trojan horse application file. | ||||
| CVE-2016-5849 | 1 Siemens | 1 Sicam Pas\/pqs | 2025-04-12 | 2.5 Low |
| Siemens SICAM PAS through 8.07 allows local users to obtain sensitive configuration information by leveraging database stoppage. | ||||
| CVE-2015-8214 | 1 Siemens | 8 Simatic Cp 343-1, Simatic Cp 343-1 Firmware, Simatic Cp 443-1 and 5 more | 2025-04-12 | N/A |
| A vulnerability has been identified in SIMATIC NET CP 342-5 (incl. SIPLUS variants) (All versions), SIMATIC NET CP 343-1 Advanced (incl. SIPLUS variants) (All versions < V3.0.44), SIMATIC NET CP 343-1 Lean (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 343-1 Standard (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 443-1 Advanced (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-1 Standard (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-5 Basic (incl. SIPLUS variants) (All versions), SIMATIC NET CP 443-5 Extended (All versions), TIM 3V-IE / TIM 3V-IE Advanced (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 3V-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0), TIM 4R-IE (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 4R-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0). The implemented access protection level enforcement of the affected communication processors (CP) could possibly allow unauthenticated users to perform administrative operations on the CPs if network access (port 102/TCP) is available and the CPs' configuration was stored on their corresponding CPUs. | ||||
| CVE-2016-7112 | 1 Siemens | 2 En100 Ethernet Module, En100 Ethernet Module Firmware | 2025-04-12 | N/A |
| A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations. | ||||